Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> RCD/RCCB/RCBO & so on >> BY3 Surge protective device
 

 

 

BY3-2.5
BY3-4.0
BY3-6.0
 
1. Usage and application scope
 
BY3 type SPD is suiting to A.C 50/60 Hz , 220V electric power system and used at the joint of the LPZ2 and LPZ3 zones. It protects the electric network shocked by the thunder or surge over voltage.
This type belongs to Class 3 and the usage condition is that there must be installed the Class 1 or Class 2 SPD, or it will be damaged by the over impulse current

 
2. Model and meaning
 
 
 
3. Technical Parameters
 
Item
BY3-2.5/150
BY3-4.0/320
BY3-6.0/420
operating voltage Un
110V AC
220V AC
220V AC
Maximum continuous operating voltage Uc
150V AC
320V AC
420V AC
Open circuit voltage ( 1.2/50µs ) Uoc
2.5kV
4.0kV
6.0kV
Insulating resistance (Risol)
> 100 M O
> 100 M O
> 100 M O
Voltage protective level Up
<800 V
< 1 kV
< 1.5 kV
Response time ns
< 100ns
< 100ns
< 100ns
Operating temperature
-40---- +85oC
-40---- +85oC
-40---- +85oC
Relative humidity
<95 %
<95 %
<95 %
Defending grade
IP20
IP20
IP20
Connection section
1 ---- 4 mm2
1 ---- 4 mm2
1 ---- 4 mm2
Earthing conductor
4mm2
4mm2
4 mm2
Wire gage
AWG-2
AWG-2
AWG-2
Installation
35 mm Rail
35 mm Rail
35 mm Rail
Outer covering material
Reinforced fire-retardant nylon PBT (Grey)
Reinforced fire-retardant nylon PBT (Grey)
Reinforced fire-retardant nylon PBT (Grey)
 
4. Installation position and application
 
1. Installed at the joint of the LPZ2 and LPZ3 zones.
2. Generally applied in computer equipment, information equipment, electronic equipment and in front of control equipment or near the socket box 220V D grade surge arrestor.
3. It adopts 35 mm DIN rail.
4. It is linked by 1 -4 mm2 copper wire, and the length of the wire can't be longer than 500mm. The earth cable should choose the double color wire which is over 4 mm2
 
 

 

 